1. Pneumatic interfaces
1.6
Diagnosis
1.6.1 Error messages of the pneumatic interfaces
Error number
Description
5
Fault in load voltage for valves
Load voltage for valves (V
or too low.
(see Parameters "Monitoring the CPX
module – Monitoring V
11
Fault short circuit at valve
Short circuit/overload at the valve
(see "Parameters" "Monitoring the
CPX module – monitoring short circuit
at valve")
13
Fault wire fracture
Monitoring residual current of valve
solenoid coils (open load, only active
with 0-signal).
(see Parameters "Monitoring wire
fracture channel x")
1)
Tolerance range of the load voltage supply V
2)
Number of faulty channel: see module diagnostic data.
Tab. 1/5: Error messages of the pneumatic interfaces
Festo P.BE-CPX-EA-EN en 0112NH
Specific faults of the pneumatic interfaces are registered or
suppressed depending on the module parametrizing.
The faults are shown on-the-spot by means of the Error LED
and, if necessary, can be evaluated with the handheld.
Depending on the module parametrization the faults are reg-
istered by the field bus node, where they can be evaluated
according to the field bus protocol used.
A pneumatic interface can register the following standard
faults:
) missing
VAL
1)
")
VAL
2)
2)
see Technical specifications in the appendix
VAL
Error treatment
Check the load voltage
•
Check the valves, whether they are
•
fitted correctly and electrical con-
nections
If necessary, replace the valve
•
Check the valves, whether they are
•
fitted correctly and electrical con-
nections
If necessary, replace the valve
•
Correct any faulty parametrizing
•
(e.g. with reserved valve locations/
blanking plates, see section 1.3)
1-15