5. Multi I/O modules
5.5

Diagnosis

5.5.1 Error messages of the multi I/O modules

Error number
Description
2
Short circuit/overload
– Short circuit/overload in sensor
supply (V
(see "Parameters" "Monitoring
the CPX module – monitoring
short circuit/overload).
or (see continuation)
Tab. 5/7: Error messages of the multi I/O modules – Part 1
5-12
Specific faults of the multi I/O modules are registered or sup-
pressed depending on the module parametrizing.
The faults are shown on-the-spot by means of the Error LED
and, if necessary, can be evaluated with the handheld.
Depending on the module parametrization the faults are reg-
istered by the field bus node, where they can be evaluated
according to the field bus protocol used.
A multi I/O module can register the following standard faults:
Error treatment
1. Eliminate short circuit/overload or
).
EL/SEN
2. Depending on parametrization (Para-
check connected sensors
meters "Reaction after short circuit"):
Setting "Switch on voltage again":
Power supply for sensors will be
switched on again automatically
when short circuit is eliminated.
Setting "Leave voltage switched
off":
– Power Off/On necessary
or
– Parameters "Modify Reaction
after short circuit" to "Switch on
voltage again".
Festo P.BE-CPX-EA-EN en 0112NH