Festo CPX Electronic Manual page 27

Hide thumbs Also See for CPX:
Table of Contents

Advertisement

1. Pneumatic interfaces
1
Printed circuit
board
2
Error LED
3
DIL switches for
configuring the
pneumatics
Fig. 1/2: DIL switches on the pneumatic interface (here for CPA pneumatics)
Festo P.BE-CPX-EA-EN en 0112NH
3. Set the DIL switch elements in accordance with the follow-
ing table. Use a suitable tool, e.g. a small screwdriver, for
setting the DIL switches.
The DIL switch contains 8 switch elements. The switches are
numbered from 1...8. The positions OPEN (CPA) or ON (Midi/
Maxi) are marked.
Rules for setting
If the number of valve solenoid coils fitted is less than the
number of output addresses set with the DIL switch, the
superfluous addresses will be reserved for later exten-
sions (if the maximum number of valves is fitted, output
addresses will then remain unused).
Modifications to the configuration will not become effec-
tive until the operating voltage is switched on again.
8 further output addresses per switch element will be
assigned for valves in the address range.
The setting of the highest-value DIL switch in the ON
(closed) position is decisive for the assigned address
range.
1
2
3
1-9