A. Technical data and Index
A.1 DeviceNet specifications of the CPV valve terminal
CP-DN8 9806NH
DeviceNet Release 1.3
The CPV valve terminal with direct link type CPV...-GE-
DN-8 operates on the DeviceNet network as a slave.
As a DeviceNet slave, the CPV valve terminal supports
the following in the assigned master/slave connection:
• explicit messages
• polled I/O messages.
"Explicit Unconnected Message Manager" (UCMM) is
not supported by the CPV valve terminal.
DeviceNet message types
As a slave device of group 2 the CPV valve terminal
supports the following types of messages:
Can identifier
10xxxxxx111
10xxxxxx110
10xxxxxx101
10xxxxxx100
xxxxxx = Node Address
GROUP 2 Message type
Duplicate MACID Check Message
Unconnected Explicit Request Message
Master I/O Poll Command Message
Master Explicit Request Message