3.6.13. Fuses

Branch circuit protection:
In order to protect the installation against electrical and fire hazard, all branch circuits in an installation, switch gear, machines etc., must be short-circuited
and over-current protected according to national/international regulations.
Short-circuit protection:
The frequency converter must be protected against short-circuit to avoid electrical or fire hazard. Danfoss recommends using the fuses mentioned below
to protect service personnel and equipment in case of an internal failure in the drive. The frequency converter provides full short-circuit protection in case
of a short-circuit on the motor output.
Over-current protection
Provide overload protection to avoid fire hazard due to overheating of the cables in the installation. The frequency converter is equipped with an internal
over-current protection that can be used for upstream overload protection (UL-applications excluded). See par. 4-18. Moreover, fuses or circuit breakers
can be used to provide the over-current protection in the installation. Over-current protection must always be carried out according to national regulations.
Fuses must be designed for protection in a circuit capable of supplying a maximum of 100,000 A
Bussmann
Bussmann
Size/
E1958
Type
JFHR2**
T/JDDZ**
P90K
FWH-
300
P110
FWH-
350
P132
FWH-
400
P160
FWH-
500
P200
FWH-
600
Table 3.4: D enclosures, 380-500 V
*170M fuses from Bussmann shown use the -/80 visual indicator, -TN/80 Type T, -/110 or TN/110 Type T indicator fuses of the same size and amperage
may be substituted for external use
**Any minimum 500 V UL listed fuse with associated current rating may be used to meet UL requirements.
Bussmann
Size/Type
E125085
JFHR2
P37K
170M3013
P45K
170M3014
P55K
170M3015
P75K
170M3015
P90K
170M3016
P110
170M3017
P132
170M3018
P160
170M4011
P200
170M4012
P250
170M4014
P315
170M5011
Table 3.5: D enclosures, 525-690 V
SIBA
LittelFuse
E4273
E180276
E71611
RKI/JDDZ
JFHR2**
JJS-
2028220-
L50S-300
300
315
JJS-
2028220-
L50S-350
350
315
JJS-
206xx32-
L50S-400
400
400
JJS-
206xx32-
L50S-500
500
500
JJS-
206xx32-
L50S-600
600
600
SIBA
Amps
E180276
JFHR2
125
2061032.125
160
2061032.16
200
2061032.2
200
2061032.2
250
2061032.25
315
2061032.315
350
2061032.35
350
2061032.35
400
2061032.4
500
2061032.5
550
2062032.55
MG.33.U2.02 - VLT
®
is a registered Danfoss trademark
(symmetrical).
rms
Fuse Tables - High Power
Ferraz-
Bussmann
Bussmann
Shawmut
E4274
E60314
H/JDDZ**
JFHR2**
A50-P300
NOS-
170M3017
300
A50-P350
NOS-
170M3018
350
A50-P400
NOS-
170M4012
400
A50-P500
NOS-
170M4014
500
A50-P600
NOS-
170M4016
600
Ferraz-Shawmut
E76491
JFHR2
6.6URD30D08A0125
6.6URD30D08A0160
6.6URD30D08A0200
6.6URD30D08A0200
6.6URD30D08A0250
6.6URD30D08A0315
6.6URD30D08A0350
6.6URD30D08A0350
6.6URD30D08A0400
6.6URD30D08A0500
6.6URD32D08A550
3. How to Install
Internal
E125085
Option
JFHR2*
Bussmann
170M3018
170M3018
170M4016
170M4016
170M4016
Internal
Option
Bussmann
170M3015
170M3015
170M3015
170M3015
170M3018
170M3018
170M3018
170M5011
170M5011
170M5011
170M5011
61