5. General Specifications
Max. terminal load (DC-1)
Max. terminal load (DC-13)
Max. terminal load (AC-1)
Max. terminal load (AC-15)
Max. terminal load (DC-1)
Max. terminal load (DC-13)
Min. terminal load on 1-3 (NC), 1-2 (NO), 4-6 (NC), 4-5 (NO)
Environment according to EN 60664-1
1) IEC 60947 part 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
Cable lengths and cross sections:
Max. motor cable length, screened/armoured
5
Max. motor cable length, unscreened/unarmoured
Maximum cross section to control terminals, flexible/ rigid wire without cable end sleeves
Maximum cross section to control terminals, flexible wire with cable end sleeves
Maximum cross section to control terminals, flexible wire with cable end sleeves with collar
Minimum cross section to control terminals
Control card performance:
Scan interval
Control characteristics:
Resolution of output frequency at 0 - 1000 Hz
Precise start/stop
Repeat accuracy of
System response time (terminals 18, 19, 27, 29, 32, 33)
Speed control range (open loop)
Speed control range (closed loop)
Speed accuracy (open loop)
Speed accuracy (closed loop), depending on resolution of feedback device
All control characteristics are based on a 4-pole asynchronous motor
Surroundings:
Enclosure
Vibration test
Max. relative humidity
Aggressive environment (IEC 60068-2-43
1)
Ambient temperature
1) For higher ambient temperature, see special conditions in the Design Guide
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance
Temperature during storage/transport
Maximum altitude above sea level without derating
Derating for high altitude, see special conditions in the Design Guide
EMC standards, Emission
EMC standards, Immunity
See section on special conditions in the Design Guide
Protection and Features:
Electronic thermal motor protection against overload.
112
1)
on 4-5 (NO) (Resistive load)
1)
on 4-5 (NO) (Inductive load)
1)
on 4-6 (NC) (Resistive load)
1)
on 4-6 (NC) (Inductive load @ cosφ 0.4)
1)
on 4-6 (NC) (Resistive load)
1)
on 4-6 (NC) (Inductive load)
(terminals 18, 19)
MG.33.U2.02 - VLT
Operating Instructions High Power
over-voltage category III/pollution degree 2
IP 00/ Chassis, IP 21/ Type 1, IP 54/ Type 12
5% - 95%(IEC 721-3-3; Class 3K3 (non-condensing) during operation
Max. 45 °C (24-hour average maximum 40 °C)
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
®
is a registered Danfoss trademark
®
VLT
Automation Drive FC 300
80 V DC, 2 A
24 V DC, 0.1A
240 V AC, 2 A
240 V AC, 0.2A
50 V DC, 2 A
24 V DC, 0.1 A
24 V DC 10 mA, 24 V AC 20 mA
150 m
300 m
1.5 mm
2
/16 AWG
1 mm
2
/18 AWG
0.5 mm
2
/20 AWG
0.25 mm
2
/ 24 AWG
1 ms
+/- 0.003 Hz
≤± 0.1 msec
≤ 2 ms
1:100 of synchronous speed
1:1000 of synchronous speed
30 - 4000 rpm: error ±8 rpm
0 - 6000 rpm: error ±0.15 rpm
0.7 g
class H
0 °C
- 10 °C
-25 - +65/70 °C
1000 m
EN 61800-3, EN 61000-6-3/4, EN 55011