VLT
Automation Drive FC 300
Operating Instructions High Power
Size/Type
P630
P710
P800
P900
P1M0
Table 3.11: F enclosures, Inverter module DC Link Fuses, 525-690 V
*170M fuses from Bussmann shown use the -/80 visual indicator, -TN/80 Type T, -/110 or TN/110 Type T indicator fuses of the same size and amperage
may be substituted for external use.
Suitable for use on a circuit capable of delivering not more than 100 000 rms symmetrical amperes, 500/600/690 Volts maximum when protected by the
above fuses.
Circuit Breaker Tables
Circuit Breakers manufactured by General Electric, Cat. No. SKHA36AT0800, 600 Vac maximum, with the rating plugs listed below can be used to meet
UL requirements.
Size/Type
P90
P110
P132
P160
P200
Table 3.12: D enclosures, 380-500 V
Non UL compliance
If UL/cUL is not to be complied with, we recommend using the following fuses, which will ensure compliance with EN50178:
In case of malfunction, not following the recommendation may result in unnecessary damage to the frequency converter.
P90 - P200
P250 - P400
Bussmann PN*
Rating
170M8611
1100 A, 1000 V
170M8611
1100 A, 1000 V
170M8611
1100 A, 1000 V
170M8611
1100 A, 1000 V
170M8611
1100 A, 1000 V
Rating plug catalog #
SRPK800A300
SRPK800A400
SRPK800A400
SRPK800A500
SRPK800A600
380 - 500 V
380 - 500 V
MG.33.U2.02 - VLT
®
is a registered Danfoss trademark
3. How to Install
Siba
20 781 32. 1000
20 781 32. 1000
20 781 32. 1000
20 781 32. 1000
20 781 32. 1000
Amps
300
400
400
500
600
type gG
type gR
3
63