5.6.3.14
Running the inverter in cavitation protection mode
Functionality
The cavitation protection will generate a fault / warning when cavitation conditions are
deemed to be present. If the inverter gets no feedback from the pump transducer, it will trip
to stop cavitation damage.
Setting parameters
Parameter
Function
P2360[0...2]
Enable cavitation protection
P2361[0...2]
Cavitation threshold [%]
P2362[0...2]
Cavitation protection time [s]
SINAMICS V20 Inverter
Operating Instructions, 07/2012, A5E03728167
Cavitation Protection Logic Diagram
Setting
This parameter enables the cavitation protection function.
= 1: Fault
= 2: Warn
This parameter defines the feedback threshold over which a
fault / warning is triggered, as a percentage (%).
Range: 0.00 ... 200.00 (factory default: 40.00)
This parameter sets the time for which cavitation conditions
have to be present before a fault / warning is triggered.
Range: 0 ... 65000 (factory default: 30)
Commissioning
5.6 Function commissioning
101