Siemens SINAMICS V20 Series Operating Instructions Manual page 126

Hide thumbs Also See for SINAMICS V20 Series:
Table of Contents

Advertisement

Parameter list
7.2 Parameter list
Parameter
Function
[1]
r0043[0...2]
Energy saved [kWh]
Displays calculated energy saved
Index:
[0]
[1]
[2]
r0050
CO / BO: Active
command data set
Displays currently active command data set.
0
1
2
Note:
See P0810
r0051[0...1]
CO: Active inverter data
set (DDS)
Displays currently selected and active inverter data set (DDS).
0
1
2
Index:
[0]
[1]
Note:
See P0820
r0052.0...15
CO / BO: Active status
word 1
Displays first active status word of inverter (bit format) and can be used to diagnose inverter status.
Bit
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
Dependency:
r0052 bit 03 "Inverter fault active": Output of bit 3 (Fault) will be inverted on digital output (Low = Fault,
High = No Fault).
Note:
See r2197 and r2198.
126
Range
Factor for kWh to CO2 conversion
-
Energy saving in kWh
Energy saving in currency
Energy saving in CO2
-
Command data set 0 (CDS)
Command data set 1 (CDS)
Command data set 2 (CDS)
-
Inverter data set 0 (DDS0)
Inverter data set 1 (DDS1)
Inverter data set 2 (DDS2)
Selected inverter data set
Active inverter data set
-
Signal name
Inverter ready
Inverter ready to run
Inverter running
Inverter fault active
OFF2 active
OFF3 active
ON inhibit active
Inverter warning active
Deviation setpoint / act. value
PZD control
|f_act| >= P1082 (f_max)
Warning: Motor current / torque limit
Brake open
Motor overload
Motor runs right
Inverter overload
Factory
Can be
default
changed
-
-
-
-
-
-
-
-
Scaling
Data
set
-
-
-
-
-
-
-
-
1 signal
Yes
Yes
Yes
Yes
No
No
Yes
Yes
No
Yes
Yes
No
Yes
No
Yes
No
SINAMICS V20 Inverter
Operating Instructions, 07/2012, A5E03728167
Data
Acc.
type
Level
Float
2
U16
2
U16
2
U16
2
0 signal
No
No
No
No
Yes
Yes
No
No
Yes
No
No
Yes
No
Yes
No
Yes

Hide quick links: