Siemens SINAMICS V20 Series Operating Instructions Manual page 207

Hide thumbs Also See for SINAMICS V20 Series:
Table of Contents

Advertisement

Parameter
Function
P2350 = 4
This tuning only changes values of P and I and should be a quarter damped response.
The option to be selected depends on the application but broadly speaking option 1 will give a good
response, whereas if a faster response is desired option 2 should be selected.
If no overshoot is desired then option 3 is the choice. For cases where no D term is wanted then option 4
can be selected.
The tuning procedure is the same for all options. It is just the calculation of P and D values that is different.
After autotune this parameter is set to zero (autotune completed).
P2354
PID tuning timeout
length [s]
This parameter determines the time that the autotuning code will wait before aborting a tuning run if no
oscillation has been obtained.
P2355
PID tuning offset [%]
Sets applied offset and deviation for PID autotuning.
Note:
This can be varied depending on plant conditions e.g. a very long system time constant might require a
larger value.
P2360[0...2]
Enable cavitation
protection
Cavitation protection enabled.
Will generate a fault / warning when cavitation conditions are deemed to be present.
SINAMICS V20 Inverter
Operating Instructions, 07/2012, A5E03728167
Range
Factory
default
60 - 65000 240
0.00 -
5.00
20.00
0 - 2
0
Cavitation Protection Logic Diagram
Can be
Scaling
changed
U, T
-
U, T
-
U, T
-
Parameter list
7.2 Parameter list
Data
Data
Acc.
set
type
Level
-
U16
3
-
Float
3
DDS
U16
2
207