Siemens SINAMICS V20 Series Operating Instructions Manual page 185

Hide thumbs Also See for SINAMICS V20 Series:
Table of Contents

Advertisement

Parameter
Function
Bit
00
01
02
03
05
06
07
08
09
10
11
12
13
14
15
r1912[0]
Identified stator
resistance [Ohm]
Displays measured stator resistance value (line-to-line). This value also includes the cable resistances.
Index:
[0]
Notice:
If the value identified (Rs = stator resistance) does not lie within the range 0.1 % < Rs [p. u.] < 100 % fault
message 41 (motor data identification failure) is issued. P0949 provides further information (fault value = 2
in this case).
Note:
This value is measured using P1900 = 2.
r1920[0]
Identified dynamic
leakage inductance
Displays identified total dynamic leakage inductance.
Index:
[0]
r1925[0]
Identified on-state
voltage [V]
Displays identified on-state voltage of IGBT.
Index:
[0]
Notice:
If the identified on-state voltage does not lie within the range 0.0V < 10V fault message 41 (motor data
identification failure) is issued. P0949 provides further information (fault value = 20 in this case).
r1926
Identified gating unit
dead time [μs]
Displays identified dead time of gating unit interlock.
P2000[0...2]
Reference frequency
[Hz]
P2000 represents the reference frequency for frequency values which are displayed / transferred as a
percentage or a hexadecimal value.
Where:
hexadecimal 4000 H ==> P2000 (e.g.: USS-PZD)
percentage 100 % ==> P2000 (e.g.: AI)
SINAMICS V20 Inverter
Operating Instructions, 07/2012, A5E03728167
Range
Signal name
Estimation of Xs
Motor ID at 2 kHz
Estimation of Tr
Estimation of Lsigma
Det. Tr meas. with 2 freq.
Measurement of on voltage
Deadtime detection from Rs measurement
MotID with hw deadtime comp activ
No deadtime detection with 2 freq
Detect Ls with LsBlock method
MotID adaption of magnetizing current
MotID adaption of main reactance
MotID switch off saturation curve optim.
MotID saturation curve optim. all framesizes
MotID saturation curve optim. big framesizes
-
U_phase
-
U_phase
-
U_phase
-
1.00 -
599.00
Factory
Can be
default
changed
-
-
-
-
-
-
-
-
50.00
T
Parameter list
7.2 Parameter list
Scaling
Data
Data
set
type
1 signal
0 signal
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
-
-
Float
-
-
Float
-
-
Float
-
-
Float
-
DDS
Float
Acc.
Level
4
4
4
2
3
185

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents