Parameter list
7.2 Parameter list
Parameter
Function
[1]
[2]
[3]
[4]
[5]
[6]
r0967
Control word 1
Displays control word 1. See r0054 for the bit field description.
r0968
Status word 1
Displays active status word of inverter (in binary) and can be used to diagnose which commands are
active. See r0052 for the bit field description.
P0969
Resettable system run
time counter
Resettable system run time counter.
P0970
Factory reset
P0970 = 1 resets all parameters (not user defaults) to their default values.
P0970 = 21 resets all parameters and all user defaults to Factory Reset state.
0
1
21
Dependency:
First set P0010 = 30 (factory settings).
Stop inverter (i.e. disable all pulses) before you can reset parameters to default values.
Note:
The following parameters retain their values after a factory reset:
r0039 CO: Energy consumption meter [kWh]
•
P0014 Store mode
•
P0100 Europe / North America
•
P2010 USS / MODBUS baudrate
•
P2011 USS address
•
P2021 MODBUS address
•
P2023 RS485 protocol selection
•
P8458 Clone control
•
When transferring P0970, the inverter uses its processor to carry out internal calculations.
Communications are interrupted for the time that it takes to make these calculations.
P0971
Transfer data from RAM
to EEPROM
Transfers values from RAM to EEPROM when set to 1.
Transfers new user default values from RAM to EEPROM when set to 21.
0
1
21
156
Range
Factory
default
Product type
Firmware version
Firmware date (year)
Firmware date (day / month)
Number of inverter objects
Firmware version
-
-
-
-
0 -
0
42949672
95
0 - 21
0
Disabled
Parameter reset
User Default Parameter Reset
0 - 21
0
Disabled
Start transfer
Start User Defaults transfer
Can be
Scaling
changed
-
-
-
-
T
-
-
-
U, T
-
Operating Instructions, 07/2012, A5E03728167
Data
Data
Acc.
set
type
Level
-
U16
3
-
U16
3
-
U32
3
-
U16
1
-
U16
3
SINAMICS V20 Inverter