Parameter list
7.2 Parameter list
Parameter
Function
Note:
See P0701. Signals above 4 V are active; signals below 1.6 V are inactive.
P0717
Connection macro
Selects a given connection macro, which is a set of parameter values for a given set of control
connections. There are a number of connection macros which define basic control connection settings
such as Terminals, BOP, PID with analog setpoint etc.
Note:
Please note that to guarantee correct setting of the Connection macro, the Connection macro number
should only be changed during Setup directly after a parameter reset.
P0719[0...2]
Selection of command &
frequency setpoint
Central switch to select control command source for inverter. Switches command and setpoint source
between freely programmable BICO parameters and fixed command / setpoint profiles. Command and
setpoint sources can be changed independently. The tens digit chooses the command source and the
units digit chooses the setpoint source.
0
1
2
3
4
5
7
40
41
42
43
44
45
47
50
51
52
53
54
55
57
Dependency:
P0719 has higher priority than P0700 and P1000.
If set to a value other than 0 (i.e. BICO parameter is not the setpoint source), P0844 / P0848 (first source
of OFF2 / OFF3) are not effective; instead, P0845 / P0849 (second source of OFF2 / OFF3) apply and the
OFF commands are obtained via the particular source defined.
BICO connections made previously remain unchanged.
Notice:
Particularly useful when e.g. changing command source temporarily from P0700 = 2.
Settings in P0719 (contrary to P0700 settings) do not reset the digital inputs (P0701, P0702, ...)
r0720
Number of digital inputs
Displays number of digital inputs.
r0722.0...12
CO / BO: Digital input
values
Displays status of digital inputs.
144
Range
Factory
default
0 - 255
0
0 - 57
0
Cmd = BICO parameter, Setpoint = BICO parameter
Cmd = BICO parameter, Setpoint = MOP setpoint
Cmd = BICO parameter, Setpoint = Analog setpoint
Cmd = BICO parameter, Setpoint = Fixed frequency
Cmd = BICO parameter, Setpoint = USS on RS232 (reserved)
Cmd = BICO parameter, Setpoint = USS on RS485
Cmd = BICO parameter, Setpoint = Analog setpoint 2
Cmd = USS on RS232 (reserved), Setpoint = BICO parameter
Cmd = USS on RS232 (reserved), Setpoint = MOP setpoint
Cmd = USS on RS232 (reserved), Setpoint = Analog setpoint
Cmd = USS on RS232 (reserved), Setpoint = Fixed frequency
Cmd = USS on RS232 (reserved), Setpoint = USS on RS232 (reserved)
Cmd = USS on RS232 (reserved), Setpoint = USS on RS485
Cmd = USS on RS232 (reserved), Setpoint = Analog setpoint 2
Cmd = USS on RS485, Setpoint = BICO parameter
Cmd = USS on RS485, Setpoint = MOP setpoint
Cmd = USS on RS485, Setpoint = Analog setpoint
Cmd = USS on RS485, Setpoint = Fixed frequency
Cmd = USS on RS485, Setpoint = USS on RS232 (reserved)
Cmd = USS on RS485, Setpoint = USS on RS485
Cmd = USS on RS485, Setpoint = Analog setpoint 2
-
-
-
-
Can be
Scaling
changed
C(1)
-
T
-
-
-
-
-
Operating Instructions, 07/2012, A5E03728167
Data
Data
Acc.
set
type
Level
-
U16
1
CDS
U16
4
-
U16
3
-
U16
2
SINAMICS V20 Inverter