Parameter list
7.2 Parameter list
Parameter
Function
Notice:
Asymmetric space vector modulation (ASVM) produces lower switching losses than space vector
modulation (SVM), but may cause irregular rotation at very low speeds.
Space vector modulation (SVM) with over-modulation may produce current waveform distortion at high
output voltages.
Space vector modulation (SVM) without over-modulation will reduce maximum output voltage available
to motor.
P1803[0...2]
Maximum modulation
[%]
Sets maximum modulation index.
Note:
P1803 = 100 %: Limit for over-control (for ideal inverter without switching delay).
P1820[0...2]
Reverse output phase
sequence
Changes sequence of phases without changing setpoint polarity.
0
1
Note:
See P1000
P1825
On-state voltage of IGBT
[V]
Corrects on-state voltage of the IGBTs.
P1828
Gating unit dead time
[μs]
Sets compensation time of gating unit interlock.
P1900
Select motor data
identification
Performs motor data identification.
0
2
Dependency:
No measurement if motor data incorrect.
P1900 = 2: Calculated value for stator resistance (see P0350) is overwritten.
Notice:
When the identification is finished P1900 is set to 0. When choosing the setting for measurement, observe
the following:
The value is actually adopted as P0350 parameter setting and applied to the control as well as being
shown in the read-only parameters below. Ensure that the motor holding brake is not active when
performing the motor identification.
Note:
Before selecting motor data identification, "Quick commissioning" has to be performed in advance.
Since the cable length of the applications differs in a wide range, the preset resistor P0352 is only a rough
estimation. Better results of the motor identification can be achieved by specifying the cable resistor before
the start of the motor identification by measuring / calculating.
Once enabled (P1900 > 0), A541 generates a warning that the next ON command will initiate
measurement of motor parameters.
Communications - both via USS as well as via the Modbus - are interrupted for the time that it takes to
make internal calculations. These calculations can take up to one minute to complete.
P1909[0...2]
Control word of motor
data identification
Control word of motor data identification.
184
Range
Factory
default
20.0 -
106.0
150.0
0 - 1
0
Forward
Reverse the Motor
0.0 - 20.0
0.9
0.00 - 3.98 0.01
0 - 2
0
Disabled
Identification of all parameters in standstill
-
0101
1100
0000
0000 bin
Can be
Scaling
changed
U, T
-
T
-
U, T
-
U, T
-
C(1), T
-
U, T
-
Operating Instructions, 07/2012, A5E03728167
Data
Data
Acc.
set
type
Level
DDS
Float
3
DDS
U16
2
-
Float
4
-
Float
4
-
U16
2
DDS
U16
4
SINAMICS V20 Inverter