Parameter
Function
P0013[0...19]
User-defined parameter
Defines a limited set of parameters to which the end user has access.
Instructions for use:
1. Set P0003 = 3 (expert user).
2. Go to P0013 indices 0 to 16 (user list)
3. Enter into P0013 index 0 to 16 the parameters required to be visible in the user-defined list.
The following values are fixed and cannot be changed:
- P0013 index 17 = 3 (user access level)
- P0013 index 18 = 10 (commissioning parameter filter)
- P0013 index 19 = 12 (key for user defined parameter)
4. Set P0003 = 0 to activate the user defined parameter.
Index:
[0]
[1]
...
[19]
Dependency:
First, set P0011 ("lock") to a different value then P0012 ("key") to prevent changes to user-defined
parameter.
Then, set P0003 to 0 to activate the user-defined list.
When locked and the user-defined parameter is activated, the only way to exit the user-defined parameter
(and view other parameters) is to set P0012 ("key") to the value in P0011 ("lock").
P0014[0...2]
Store mode
Sets the store mode for parameters. The store mode can be configured for all interfaces under "Index".
0
1
Index:
[0]
[1]
[2]
Note:
An independent store request may be part of the serial communications (for example, PKE bits 15-12 of
USS protocol). See the table below for an influence on the settings of P0014.
Value of P0014 [x]
1. P0014 itself will always be stored in the EEPROM.
2. P0014 will not be changed by performing a factory reset (P0010 = 30 and P0970 = 1).
When transferring parameter P0014, the inverter uses its processor to carry-out internal calculations.
Communications - both via USS as well as Modbus - are interrupted for the time that it takes to make
these calculations.
r0018
Firmware version
Displays version number of installed firmware.
SINAMICS V20 Inverter
Operating Instructions, 07/2012, A5E03728167
Range
0 - 65535
1st user parameter
2nd user parameter
...
20th user parameter
0 - 1
Volatile ( RAM)
Non-volatile (EEPROM)
USS on RS485
USS on RS232 (reserved)
Reserved
RAM
EEPROM
RAM
EEPROM
-
Factory
Can be
default
changed
[0...16] 0
U, T
[17] 3
[18] 10
[19] 12
0
U, T
Store request via USS
EEPROM
EEPROM
RAM
RAM
-
-
Parameter list
7.2 Parameter list
Scaling
Data
Data
set
type
-
-
U16
-
-
U16
Result
EEPROM
EEPROM
RAM
EEPROM
-
-
Float
Acc.
Level
3
3
1
123