Parameter list
7.2 Parameter list
Parameter
Function
r2379.0...1
CO / BO: Motor staging
status word
Output word from the motor staging feature that allows external connections to be made.
Bit
00
01
P2380[0...2]
Motor staging hours run
[h]
Displays hours run for external motors. To reset the running hours, set the value to zero, any other value is
ignored.
Example:
P2380 = 0.1 ==> 6 min
60 min = 1 h
Index:
[0]
[1]
[2]
P2800
Enable FFBs
Free function blocks (FFB) are enabled in two steps:
1. P2800 enables all free function blocks (P2800 = 1).
2. P2801 and P2802 respectively, enable each free function block individually. Additionally fast free
function blocks can be enabled via P2803 = 1.
0
1
Dependency:
All active function blocks will be calculated in every 128 ms, fast free function blocks in every 8 ms.
P2801[0...16]
Activate FFBs
P2801 and P2802 respectively, enable each free function block individually (P2801[x] > 0 or P2802[x] > 0).
In addition, P2801 and P2802 determine the chronological order of each function block by setting the level
in which the free function block will work.
The following table shows that the priority decreases from right to left and from top to bottom.
0
212
Range
-
Signal name
Start motor 1
Start motor 2
0.0 -
42949672
0.0
Motor 1 hrs run
Motor 2 hrs run
Not used
0 - 1
Disable
Enable
0 - 6
Not Active
Factory
Can be
default
changed
-
-
0.0
U, T
0
U, T
0
U, T
Scaling
Data
set
-
-
1 signal
Yes
Yes
-
-
-
-
-
-
SINAMICS V20 Inverter
Operating Instructions, 07/2012, A5E03728167
Data
Acc.
type
Level
U16
3
0 signal
No
No
Float
3
U16
3
U16
3