No.
Functions
38
39
Aux. output 6
40
Mains
A-phase
41
voltage input
Mains
B-phase
42
voltage input
Mains
C-phase
43
voltage input
44
Mains N-wire input
Gen Bus A-phase
45
voltage input
Gen Bus B-phase
46
voltage input
Gen Bus C-phase
47
voltage input
Gen
Bus
N-wire
48
input
49
CT A-phase input
50
CT B-phase input
51
CT C-phase input
52
CT COM
53
Gen Bus A-phase
54
current input
55
Aux. Input 8
56
57
58
Reserved
59
60
61
NOTE1: USB port on back panel is parameter configuration port and can set controller on PC.
NOTE2: Ethernet port on back panel is network monitoring port, and can monitor controller on PC.
HGM8156 Genset Parallel (With Mains) Controller
HGM8156 GENSET PARALLEL CONTROLLER USER MANUAL
Cable Size
2
2.5mm
Public points of relay
2
2.5mm
Normally open outputs, rated 8A
2
2.5mm
Public points of relay
2
1.0mm
Connects to A-phase of mains(2A fuse is recommended)
2
1.0mm
Connects to B-phase of mains (2A fuse is recommended)
2
1.0mm
Connects to C-phase of mains (2A fuse is recommended)
2
1.0mm
Connects to N-wire of mains
Connects to A-phase of gen bus output
2
1.0mm
(2A fuse is recommended)
Connects to B-phase of gen bus output
2
1.0mm
(2A fuse is recommended)
Connects to C-phase of gen bus output
2
1.0mm
(2A fuse is recommended)
2
1.0mm
Connects to N-wire of gen bus output
2
1.5mm
Outside connects to secondary coil of CT (rated 5A)
2
1.5mm
Outside connects to secondary coil of CT (rated 5A)
2
1.5mm
Outside connects to secondary coil of CT (rated 5A)
2
1.5mm
Refer to following installation instruction;
2
1.5mm
Outside connects secondary coil of CT (rated 5A)
2
1.5mm
2
1.0mm
Ground connected is active (B-)
/
Reserved terminal; Please don't connect wires.
Remark
2019-09-10
Version 1.1
Table 14.
For details please
see Table 15.
Page 20 of 44