PARAMETER SETTING

CAUTION! Please change controller parameters when generator is in standby mode (e.g. configurable input,
configurable output, various delay etc.), otherwise shutdown alarm or other abnormal phenomenon may occur. .
NOTES:
1) Maximum value must be over minimum set value in case that too high and too low may happen at the same time;
2) When warning alarm is being set, please set the correct return value; otherwise it may cause abnormal alarms. When
maximum value is being set, return value shall be less than the set value; when minimum value is being set, return value
must be over set value;
3) Configurable inputs could not be set the same item; otherwise, there may be abnormal functions. However, configurable
outputs can be set to the same item.
HGM8156 Genset Parallel (With Mains) Controller
HGM8156 GENSET PARALLEL CONTROLLER USER MANUAL
2019-09-10
Version 1.1
Page 33 of 44