Smartgen HGM8156 User Manual page 32

Genset busbar parallel (with mains) controller
Table of Contents

Advertisement

No.
Type
Reset
Maintenance
24
Alarm
25-27 Reserved
Remote Start
28
(On Load)
Remote Start
29
(Off Load)
30
Manual Start Aux
Remote Start
31
(On Demand)
32
Remote Start Island
33
Simulate Stop Button
34
Simulate Manual Button
35
Reserved
36
Simulate Auto Button
37
Simulate Start Button
Simulate
38
Close/Open Button
Simulate
39
Close/Open Button
40
Reserved
41-44 Reserved
45
Simulate Mains Normal
Simulate
46
Abnormal
47-55 Reserved
HGM8156 Genset Parallel (With Mains) Controller
HGM8156 GENSET PARALLEL CONTROLLER USER MANUAL
Description
Controller will set maintenance time and date as default when input is
active.
In Auto mode, when input is active, genset can be started and takes
load after genset running normal; when input is inactive, genset will
stop automatically.
In Auto mode, when input is active, genset can be started and takes
off load after genset running normal; when input is inactive, genset
will stop automatically.
In Auto mode, when input is active, genset will start automatically;
when input is inactive, genset will stop automatically;
In Auto mode, when input is active, genset will start/stop according to
load;
In Auto mode, when input is active, genset will start automatically and
takes load after normal running, mains unloads; when input is
inactive, mains takes load and genset unloads and stops
automatically;
An external button can be connected and pressed as the simulate
panel key.
Bus
An external button can be connected and pressed as the simulate
panel key.
Mains
In Auto mode, when input is active, it means mains is normal;
Mains
In Auto mode, when input is active, it means mains is abnormal;
2019-09-10
Version 1.1
Page 32 of 44