6

PROTECTIONS

6.1 WARNING ALARMS

When controller detects warning signals, it only issues warnings, not shutdown the genset.
No
Type
1
Battery Over Volt
2
Battery Under Volt
3
Maintenance Due
4
Digital Input
5
Fail to sync
6
Genset Number Few
7
Bus Capacity Low
Mains Output Power
8
Limit
9
Mains Over Freq
10
Mains Under Freq
11
Mains Over Voltage
12
Mains Under Voltage
13
Mains ROCOF
14
Mains Vector Shift
HGM8156 Genset Parallel (With Mains) Controller
HGM8156 GENSET PARALLEL CONTROLLER USER MANUAL
Table 8 Warning Alarms
When the controller detects that start battery voltage has exceeded the
pre-set value, it will initiate a warning alarm.
When the controller detects that start battery voltage has fallen below
the pre-set value, it will initiate a warning alarm.
When count down time is 0 and the action is selected "Warn", it will
initiate a warning alarm.
When digit input port is set as warning and the alarm is active, it will
initiate a warning alarm.
When the controller does not detect synchronization signal within the
pre-set synchronization time, it will initiate a warning alarm.
Least start genset number is not reached when start request delay is
over, it will initiate a warning alarm.
When current power percentage of bus is above 100% and alarm action
is selected to Warn, it will initiate a warning alarm.
When mains power is above pre-set output power limit and alarm action
is selected Warn, it will initiate a warning alarm.
When controller detects mains frequency is over pre-set limit, it initiates
a warning signal.
When controller detects mains frequency is below pre-set limit, it
initiates a warning signal.
When controller detects mains voltage is over pre-set limit, it initiates a
warning signal.
When controller detects mains voltage is below pre-set limit, it initiates a
warning signal.
When controller detects mains ROCOF is over pre-set limit, it initiates a
warning signal.
When controller detects mains vector change is over pre-set limit, it
initiates a warning signal.
Description
2019-09-10
Version 1.1
Page 16 of 44