Installing Output Devices

The control supports up to 96 outputs. Each device must be programmed as to how to act (ACTION), when to activate
(START), and when to deactivate (STOP). A total of 15 4204 relay modules may be used and supports up to 60 outputs.
A total of 96 outputs is obtained using 96 4101SN's. The 4204 and 4101SN may be used in conjunction with each
other, until programming the maximum of 96 outputs.
Installing a 4204 Relay Module
ULC
Relay modules have not been evaluated for ULC installations.
Each 4204 module provides four Form C (normally open and normally closed) relays.
The relay module will not operate until the device address you have set the DIP switches for is enabled in
the control's Device Programming in the #93 Menu Mode.
1.
Set the 4204 dip switches for a device address 01-15, refer to Figure 12 below.
Do not use an address being used by another device (keypads, RF receivers, etc.).
2.
Mount the 4204 Module per the instructions provided with them.
3.
Connect the module's wire harness to the control (6, 7, 8, and 9). Plug the connector (other end of
harness) to the module.
If you are mounting remotely, homerun each module to the control. Refer to the table on page 11.

Figure 12: 4204 Relay Module

4-13
SECTION 4: INSTALLING THE CONTROL