Section 9
Control functions
Table 1309:
DCXSWI Non group settings (Advanced)
Parameter
Operation counter
Adaptive pulse
Event delay
Vendor
Serial number
Model
Table 1310:
ESXSWI Non group settings (Basic)
Parameter
Operation
Select timeout
Pulse length
Control model
Operation timeout
Identification
Table 1311:
ESXSWI Non group settings (Advanced)
Parameter
Operation counter
Adaptive pulse
Event delay
Vendor
Serial number
Model
9.1.8
1362
Values (Range)
Unit
0...10000
0=False
1=True
0...60000
ms
Values (Range)
Unit
1=on
5=off
10000...300000
ms
10...60000
ms
0=status-only
1=direct-with-
normal-security
4=sbo-with-
enhanced-security
10...60000
ms
Values (Range)
Unit
0...10000
0=False
1=True
0...60000
ms

Monitored data

Table 1312:
CBXCBR Monitored data
Name
POSITION
Step
Default
1
0
1=True
1
10000
0
0
0
Step
Default
1=on
10000
30000
1
100
4=sbo-with-
enhanced-security
1
30000
ESXSWI1 switch
position
Step
Default
1
0
1=True
1
10000
0
0
0
Type
Values (Range)
Dbpos
0=intermediate
1=open
2=closed
3=faulty
1MRS759142 C
Description
Nr of opening operations
Deactivate control pulse when apparatus
has reached correct position
Event delay of the intermediate and faulty
position
External equipment vendor
External equipment serial number
External equipment model
Description
Operation mode on/off
Select timeout in ms
Open and close pulse length
Select control model
Timeout for negative termination
Control Object identification
Description
Nr of opening operations
Deactivate control pulse when apparatus
has reached correct position
Event delay of the intermediate and faulty
position
External equipment vendor
External equipment serial number
External equipment model
Unit
Description
Apparatus position
indication
Technical Manual
REX640