ABB RELION REX640 Technical Manual page 1453

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
REX640
Technical Manual
Name
Type
FR_BUSA_MEAS
FLOAT32
FR_BUSB_MEAS
FLOAT32
U_DIFF_SYNC
BOOLEAN
FR_DIFF_SYNC
BOOLEAN
PH_DIF_SYNC
BOOLEAN
SLIP_ACCL
FLOAT32
ACT_ASC_CB
INT32
CB_CL_BLKD
Enum
SYNCCHK_STS
Enum
LIVEDEAD_STS
Enum
ASNSCSYN
Enum
Values (Range)
Unit
35.00...75.00
Hz
35.00...75.00
Hz
0=False
1=True
0=False
1=True
0=False
1=True
0.000...5.000
xFn/s
0...2147483647
1=Unblocked
2=Ext Check Fail
3=IED Test CB
Service
4=IED Service
CB Test
1=Off
2=Synchronous
3=Asynchronous
-1=Off
1=Both Dead
2=Live B, Dead A
3=Dead B, Live A
4=Dead A, B Any
5=Dead B, A Any
6=One Live,
Dead
7=Not Both Live
1=on
2=blocked
3=test
4=test/blocked
5=off
Section 9
Control functions
Description
Calculated bus A
frequency
Calculated bus B
frequency
Voltage difference out of
limit for synchronizing
Frequency difference out
of limit for synchronizing
Phase angle difference
out of limit for
synchronizing
Calculated rate of change
of frequency slip
Active ASCGAPC host
circuit breaker number
CB close blocked status
Synchro check mode
status
Live dead mode status
Status
1447

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents