is activated as an indication of a failed closing attempt. The closing pulse is not
delivered if the closing conditions become valid after Maximum Syn time has elapsed.
The closing pulse is delivered only once for each activated external command signal,
and a new closing-command sequence cannot be started until the external command
signal is reset and reactivated. The SYNC_INPRO output is active when the closing-
command sequence is in progress and it is reset when the CL_COMMAND input is reset
or Maximum Syn time has elapsed.
Bypass mode
SECRSYN can be set to the bypass mode by setting the parameters Synchrocheck
mode and Live dead mode to "Off" or alternatively by activating the BYPASS input.
In the bypass mode, the closing conditions are always considered to be fulfilled by
SECRSYN. Otherwise, the operation is similar to the normal mode.
Voltage angle difference adjustment
In application where the power transformer is located between the voltage
measurement and the vector group connection gives phase difference to the voltages
between the high- and low-voltage sides, the angle adjustment can be used to meet
synchronism.
ϕ
U_Bus
U_Line
GUID-9595B1ED-F40B-441F-98E2-4B6129DF4FED V1 EN
Figure 746:
Angle difference when power transformer is in sychrocheck zone
Section 9
Control functions
U_Bus
U_Line
1393