ABB RELION REX640 Technical Manual page 1177

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
REX640
Technical Manual
This logic uses the start signal of the reverse-looking zone (Z3) connected to the IRV
input, which is used to recognize the fault in the reverse direction, that is, in the parallel
feeder. When the reverse zone is activated after a start delay (the Reversal time
setting), the logic is ready to issue an OPR_IRV output signal. The OPR_IRV signal
is connected to the BLK_CS_OPR input of DSOCPSCH in order to block the sending
of the carrier send signal (CS) and the activation of the OPERATE output of the
communication logic. The OPR_IRV signal has a drop-off delay defined with the
Reversal reset time setting.
An internal 10 ms drop-off timer enables the current reversal logic to
be activated for the short-duration input signals even if the Reversal
reset time setting is set to zero.
The BLK_IRV input is used to block the activation of the OPR_IRV output. The
BLK_IRV input is typically connected to the forward-looking zone start signals
within the terminal. General blocking is achieved by activating the BLOCK input.
Weak-end infeed logic
Weak-end infeed logic is used to activate the distance protection function when the
fault current infeed is too low due to, for example, high source impedance or fault
current distribution between sources. When activated, the CR signal is logically
combined with the local criteria to initiate the tripping of the weak-end breaker. The
received signal is echoed back to accelerate the tripping in the opposite end with the
stronger source.
CB_OPEN
U_AB
U_BC
U_CA
U3P
U_A
U_B
U_C
CR
BLK_WEI1
BLK_WEI2
FF
BLOCK
GUID-5874AF6F-D7B5-405F-BA24-6260B1F2003A V1 EN
Figure 631:
Functional module diagram of weak-end infeed logic
The WEI logic is enabled using the Wei mode setting.
If Wei mode= "Off", the WEI logic is disabled.
If Wei mode= "Echo", the WEI logic is enabled without Level detector.
If Wei mode= "Echo and Operate", the WEI logic is enabled with Level detector.
Protection related functions
Level
Weak end
detector
trip logic
Echo
logic
Section 5
OPR_WEI
ECHO
CR
1171