resonance curve. An example of the linearization table is given in
corresponding linearization curve is plotted in
The values put in ascending order are automatically adjusted so they are in the
neighboring positions of the array, irrespective of the position in the linearization
table.
Table 1430:
Example of a linearization table
Potentiometer value (setting Pot value x, x = 1...10) Coil position (setting Coil current x, x = 1...10)
100
150
200
250
300
350
400
450
600
1000
100
90
80
70
60
50
40
30
20
10
0
0
200
GUID-BDB8E42D-335F-4A75-8A82-F50A0FACBDAA V1 EN
Figure 825:
Example of a linearization curve
Aged ASCs can suffer from wearing of the position-indicating potentiometer. The
potentiometer gaps are identified during the calibration and the number of the gaps is
displayed on the HMI after the calibration. Actual gap locations GAP_LO_VAL_x
and GAP_HI_VAL_x (x = 1...5, which corresponds to the gap identification number)
Figure
825.
10
20
30
37
43
48
53
57
68
90
400
600
Potentiometer value [Ω]
Section 9
Control functions
Table 1430
and the
800
1000
1589