ABB RELION REX640 Technical Manual page 1185

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
REX640
Technical Manual
Current reversal logic
Current reversal logic is enabled by changing the value of the Reversal mode setting to
"On".
Current reversal logic uses the start signal of the reverse directional residual
overcurrent function connected to the IRV input, which is used to recognize the fault
in the reverse direction, that is, in the parallel feeder. When the reverse directional
residual overcurrent function is activated, the logic is ready to issue an OPR_IRV
output signal after a start delay (setting Reversal time). The OPR_IRV signal is
connected to the BLK_CS_OPR input of the scheme communication logic function to
block the sending of the carrier send signal (CS) and the activation of the OPERATE
output of the communication logic. The OPR_IRV signal has a drop-off delay defined
with the Reversal reset time setting.
An internal 10 ms drop-off timer is provided which ensures the current
reversal logic is activated for short-duration input signals, even if the
Reversal reset time setting is set to zero.
The BLK_IRV input is used to block the activation of the OPR_IRV output. The
BLK_IRV input is typically connected to the start signals of the forward-looking
residual overcurrent function in the terminal. General blocking is achieved by
activating the BLOCK input.
Weak-end infeed (WEI) logic
The WEI logic is used to activate the residual overcurrent protection function when
the fault current infeed is too low due to, for example, high source impedance or fault
current distribution between sources. When activated, the carrier receive (CR) signal
is logically combined with the local criteria to initiate the tripping of the weak-end
breaker. The received signal is also echoed back to accelerate the tripping at the
opposite end with the stronger source.
CB_OPEN
Level
Uo
URES
detector
CR
BLK_WEI1
BLK_WEI2
FF
BLOCK
GUID-48942739-E438-4C52-B5B0-7E575FA89A33 V1 EN
Figure 636:
Functional module diagram of Weak-end infeed logic
The WEI logic is enabled using the Wei mode setting.
Protection related functions
Weak end
OPR_WEI
trip logic
Echo
logic
Section 5
ECHO
CR
1179