Section 9
Control functions
1518
If the cut-out time elapses
If the reclaim time elapses and the AR function is ready for a new sequence
If the AR function is in lockout or disabled, that is, if the value of the Protection
crd mode setting is "AR inoperative" or "AR inop, CB man".
The PROT_CRD output can also be controlled with the Protection crd mode setting.
The setting has the following modes:
"no condition": the PROT_CRD output is controlled only with the Protection crd
limit setting
"AR inoperative": the PROT_CRD output is active, if the AR function is disabled
or in the lockout state, or if the INHIBIT_RECL input is active
"CB close manual": the PROT_CRD output is active for the reclaim time if the
circuit breaker has been manually closed, that is, the AR function has not issued
a close command
"AR inop, CB man": both the modes "AR inoperative" and "CB close manual" are
effective
"always": the PROT_CRD output is constantly active
PHLPTOC
I_A
OPERATE
I_B
START
I_C
BLOCK
ENA_MULT
CB_POSITION
CB_READY
GUID-82D13A61-B11B-4653-84EC-B5A89E223817 V1 EN
Figure 800:
Configuration example of using the PROT_CRD output for protection
blocking
If the Protection crd limit setting has the value "1", the instantaneous three-phase
overcurrent protection function PHIPTOC is disabled or blocked after the first shot.
Circuit breaker controller
Circuit breaker controller contains two features: SOTF and frequent-operation
counter. SOTF protects the AR function in permanent faults.
The circuit breaker position information is controlled with the CB closed Pos status
setting. The setting value "TRUE" means that when the circuit breaker is closed, the
CB_POS input is TRUE. When the setting value is "FALSE", the CB_POS input is
DARREC
INIT_1
OPEN_CB
INIT_2
CLOSE_CB
INIT_3
CMD_WAIT
INIT_4
PROT_CRD
PROT_DISA
INIT_5
INIT_6
INPRO
DEL_INIT_2
LO CKED
DEL_INIT_3
UNSUC_RECL
DEL_INIT_4
AR_ON
BLK_RECL_T
BLK_RCLM_T
BLK_THERM
CB_POS
CB_READY
DISA_COUNT
INC_SHOTP
INHIBIT_RECL
RECL_ON
SYNC
1MRS759142 C
OR
CB_TRIP
CB_CLOSE
REX640
Technical Manual