ABB RELION REX640 Technical Manual page 1593

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
REX640
Technical Manual
functionality is enabled (Resistor control = "Automatic") and the EARTH_FAULT
output is active. The resistor control sequence after the earth-fault indication depends
on the resistor connection status during the healthy state. The healthy-state status is
selected with the Resistor healthy St setting. The available options are "On" and
"Off". The settings affecting the control sequence are explained in
Resistor healthy St
setting
"Off"
Switch on
delay 1
Switch off
delay 1
"On"
EARTH_FAULT
GUID-6A1A08CF-4455-4887-AF04-ACD27FDFD2B0 V1 EN
Figure 824:
Resistor control sequence
When the earth-fault indication becomes inactive, both the single sequence and the
repeat sequences are finished and the resistor is switched back to its initial state.
The resistor control sequence contains a repeat part which can be repeated after the
whole sequence is executed once. The number of repetitions can be selected with
Resistor repeats setting. Additionally, the pause between the consecutive repeats can
be selected with Resistor pause setting. After the sequences are completed, the initial
resistor healthy state is restored within 1 s if the Resistor healthy St = "On". If the
healthy state is "Off", the resistor is already in its healthy-state position after the
sequence is completed.
It is also possible to manually trigger the resistor control sequence with
ST_RESIS_SEQ binary input.
Blocking
The BLK_AUTO input blocks the automatic operation of the function. PASANCR's
automatic operation is blocked internally if the ASC is disconnected at the substation,
that is, COIL_STS signal is low. The BLK_MANUAL input blocks the manual control
of the coil. The BLK_RESISTOR input disconnects the parallel resistor and blocks its
switching on, for example, due to resistor overheating.
Resistor control sequence during
earth-fault
Time on 1
Switch on
delay 2
Repeat part
Switch off
delay 2
Time off 1
Repeat part
Section 9
Control functions
Figure
824.
Time on 2
Time
1587

Hide quick links: