Section 9
Control functions
1354
GUID-6DADD287-2569-49BE-B942-C8D636F2178D V1 EN
Figure 721:
Enabling and blocking logic for CLOSE_ENAD and OPEN_ENAD
signals
Opening and closing operations
The opening and closing operations are available via communication, binary inputs or
LHMI commands. As a prerequisite for control commands, there are enabling and
blocking functionalities for both opening and closing commands (CLOSE_ENAD and
OPEN_ENAD signals). If the control command is executed against the blocking or if
the enabling of the corresponding command is not valid, CBXCBR, DCXSWI and
ESXSWI generate an error message.
When close command is given from communication, via LHMI or activating the
AU_CLOSE input, it is carried out (the EXE_CL output) only if CLOSE_ENAD is
TRUE.
If the SECRSYN function is used in "Command" mode, the CL_REQ output can be
used in CBXCBR. Initially, the SYNC_OK input is FALSE. When the close command
given, it activates the CL_REQ output, which should be routed to SECRSYN. The
close command is then processed only after SYNC_OK is received from SECRSYN.
When using SECRSYN in the "Command" mode, the CBXCBR
setting Operation timeout should be set longer than SECRSYN
setting Maximum Syn time.
1MRS759142 C
REX640
Technical Manual