Section 5
Protection related functions
1072
Table 1009:
Retrip logic operation
Value of setting CB fail
Value of setting CB
retrip mode
failure mode
Off
Current
Breaker status
Both(AND)
Both(OR)
Without Check
Current
Breaker status
Both(AND)
Both(OR)
Current check
Current
Breaker status
Both(AND)
Both(OR)
TRRET activation is blocked if either CB_FAULT_AL output (from
Timer 3) is active or the BLOCK input is activated.
Once activated, TRRET remains active for the set Trip pulse time or until the reasons
for activation are reset. TRRET is also reset if CB_FAULT_AL or BLOCK is activated.
Retrip functionality
Retrip functionality switched off. TRRET is not
activated.
TRRET is activated after Timer 1 elapses.
TRRET is activated after Timer 1 elapses and any
Current value setting.
phase current exceeds
TRRET is activated after Timer 1 elapses and CB is
in closed position.
TRRET is activated after Timer 1 elapses and CB is
in closed position and any phase current exceeds
Current value setting.
TRRET is activated after Timer 1 elapses and
either of the following is true:
CB is in closed position.
Any phase current exceeds
setting.
1MRS759142 C
Current value
REX640
Technical Manual