ABB RELION REX640 Technical Manual page 1048

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 4
Protection functions
Parameter
Operating curve type
Operate delay time
Alarm delay time
Table 979:
HCUBPTOC Group settings (Advanced)
Parameter
Natural Comp Ena PhA
Natural Comp Ena PhB
Natural Comp Ena PhC
Table 980:
HCUBPTOC Non group settings (Basic)
Parameter
Operation
Curve parameter A
Curve parameter B
Curve parameter C
Curve parameter E
Table 981:
HCUBPTOC Non group settings (Advanced)
Parameter
Reset delay time
Minimum operate time
1042
Values (Range)
Unit
1=ANSI Ext. inv.
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
40...200000
ms
40...200000
ms
Values (Range)
Unit
0=False
1=True
0=False
1=True
0=False
1=True
Values (Range)
Unit
1=on
5=off
0.00860...120.0000
0
0.00000...0.71200
0.02...2.00
0.0...1.0
Values (Range)
Unit
0...60000
ms
20...60000
ms
Step
Default
15=IEC Def. Time
10
5000
10
200000
Step
Default
0=False
0=False
0=False
Step
Default
1=on
1
28.20000
1
0.12170
1
2.00
1
1.0
Step
Default
1
20
1
20
1MRS759142 C
Description
Selection of time delay curve type
Operate delay time
Alarm delay time
Description
Enable natural unbalance compensation
PhA
Enable natural unbalance compensation
PhB
Enable natural unbalance compensation
PhC
Description
Operation Off / On
Parameter A for customer programmable
curve
Parameter B for customer programmable
curve
Parameter C for customer programmable
curve
Parameter E for customer programmable
curve
Description
Reset delay time
Minimum operate time for IDMT curves
Technical Manual
REX640