Section 9
Control functions
Parameter
Position Meas mode
Resistor control
Resistor Nom value
Coil losses
Fix coil value
Fix coil losses
Pot Max gap
Fix coil type
Level detector op
Pot value 1
Coil current 1
Pot value 2
Coil current 2
Pot value 3
Coil current 3
Pot value 4
Coil current 4
Pot value 5
Coil current 5
Pot value 6
Coil current 6
Pot value 7
Coil current 7
Pot value 8
Coil current 8
Pot value 9
Coil current 9
Pot value 10
Coil current 10
1594
Values (Range)
Unit
1=Pos. indication
2=Pos. ind. and
meas.
1=OFF
2=ON
3=Automatic
0.00...100.00
ohm
0.00...20.00
%
0...10000
A
0.00...20.00
%
0...100
%
1=OFF
2=ON
3=Automatic
0=Disable
1=Enable
0...3000
ohm
0...10000
A
0...3000
ohm
0...10000
A
0...3000
ohm
0...10000
A
0...3000
ohm
0...10000
A
0...3000
ohm
0...10000
A
0...3000
ohm
0...10000
A
0...3000
ohm
0...10000
A
0...3000
ohm
0...10000
A
0...3000
ohm
0...10000
A
0...3000
ohm
0...10000
A
Step
Default
1=Pos. indication
1=OFF
0.01
5.00
0.01
2.00
1
0
0.01
2.00
1
5
1=OFF
1=Enable
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1MRS759142 C
Description
Coil position measurement mode
Resistor control mode
Nominal resistance of the parallel resistor
at power auxiliary winding secondary
voltage level
Coil losses
Inductive current produced by fixed coil at
fixed coil nominal voltage level
Fix coil losses
Potentiometer maximum gap length
Fix coil type
Enable / disable level detector module
Potentiometer value 1
Coil current 1
Potentiometer value 2
Coil current 2
Potentiometer value 3
Coil current 3
Potentiometer value 4
Coil current 4
Potentiometer value 5
Coil current 5
Potentiometer value 6
Coil current 6
Potentiometer value 7
Coil current 7
Potentiometer value 8
Coil current 8
Potentiometer value 9
Coil current 9
Potentiometer value 10
Coil current 10
Technical Manual
REX640

Hide quick links:

Advertisement

Table of Contents
loading