1MRS759142 C
REX640
Technical Manual
In
Figure
620, in case of internal faults, the CS_BLOCKING signal is not sent because
the fault is not sent as it is not seen by the reverse-looking zones (Z3).
Z3
Bus A
~
3
Z2_START
GUID-41FB8590-EDBD-4EBB-A99C-0E0CBFB7E9C0 V1 EN
Figure 620:
Simplified functional diagram of the blocking scheme, internal fault
In
Figure
621, in case of external faults, the protection relay at bus B sees the fault in
the reverse direction and sends a blocking signal CS_BLOCKING to the protection
relay at bus A. There is no CB operation at either end.
Z3
Bus A
~
3
Z2_START
GUID-D6308D07-F72A-4B2A-9E04-2B25050647DA V1 EN
Figure 621:
Simplified functional diagram of the blocking scheme, external fault
Protection related functions
Z2
Z1
Z1
Z2
TRIP_CB_A
Z2_START
Z2
Z1
Z1
Z2
Z3_START
Section 5
Bus B
~
3
Z3
TRIP_CB_B
Bus B
~
3
Z3
1145