ABB RELION REX640 Technical Manual page 1637

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
REX640
Technical Manual
"Single Phase". For the selection "Three Phase" of Phase mode, no event indication or
any activation takes place due to a non-active phase.
Voltage swell set
Voltage dip set
Voltage Int set
ST_A
ST_B
ST_C
SWELLST
DIPST
INTST
SWELLOPR
DIPOPR
INTOPR
GUID-4F977366-4415-407A-88A7-BCDE92CBB75D V1 EN
Figure 842:
Concurrent dip and swell when Phase mode is "Single Phase"
In
Figure
843, one phase is in dip and two phases have a swell indication. For the
Phase mode value "Three Phase", the activation occurs only when all the phases are
active. Furthermore, both swell and dip variation event detections take place
simultaneously. In case of a concurrent voltage dip and voltage swell, both
SWELLCNT and DIPCNT are incremented by one.
Also
Figure 843
shows that for the Phase mode value "Single Phase", two different
time moment variation event swell detections take place and, consequently, DIPCNT
is incremented by one but SWELLCNT is totally incremented by two. In
842
and
Figure 843
it is assumed that variation durations are sufficient for detections
to take place.
Power quality measurement functions
U_A
U_C
U_B
Section 10
TRUE
FALSE
TRUE
FALSE
TRUE
FALSE
TRUE
FALSE
TRUE
FALSE
TRUE
FALSE
TRUE
FALSE
TRUE
FALSE
TRUE
FALSE
bothFigure
1631