Operation Principle - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
9.11.6
REX640
Technical Manual
FIXCOIL, OP_FIXCOIL and CL_FIXCOIL: Status signal and corresponding
open and close command signals for controlling the circuit breaker or
disconnector of the fixed parallel coil. These signals are applied if a fixed parallel
coil is installed in the system.
RESISTOR, OP_RESISTOR and CL_RESISTOR: Status signal and
corresponding open and close command signals for controlling the contactor,
circuit breaker or disconnector of the parallel resistor. These signals are applied
if a parallel resistor is installed in the system.
An example configuration of the connections is shown in
inputs are indicated with red lines and outputs with green lines. This example shows
a simple, one-controller setup without the parallel resistor of the coil.
COIL
GUID-D6AF8AD7-CAE2-4BAD-BA75-961E825651B1 V1 EN
Figure 818:
Example configuration of the controller connections

Operation principle

The Operation setting is used to enable or disable the function. The corresponding
parameter values are "on" and "off".
The operation of PASANCR can be described with a module diagram. All the
modules in the diagram are explained in the next sections.
I
A
E
A
I
B
E
B
I
C
E
C
Optional
Section 9
Control functions
Figure
818. Controller
PASANCR
U3P
RAISE_OWN
IRES
LOWER_OWN
URES
FIXCOIL
COIL_POS
OP_FIXCOIL
COIL_STS
CL_FIXCOIL
FIXCOIL_STS
RESISTOR
RESISTOR_STS
OP_RESISTOR
HIGH_LIMIT
CL_RESISTOR
LOW_LIMIT
ALARM
ST_CALIB
MOT_ALARM
ST_TUNING
POT_ALARM
ST_RESIS_SEQ
EARTH_FAULT
RAISE_LOCAL
TUNING_ACT
LOWER_LOCAL
BLK_AUTO
BLK_MANUAL
BLK_RESISTOR
1575