ABB RELION REX640 Technical Manual page 1465

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
REX640
Technical Manual
Source participation group
Group 6
Group 7
Group 8
Group 9
The participation group number for source 1...source 9 is available in the monitored
output SRC1_PTC_GRP...SRC8_PTC_GRP.
Any source can be nominated for participation in voltage and frequency matching
from the command parameter Source1 selected...Source8 selected. This selection is
confirmed from the command parameter Confirm source Sel. The selected
participation group information is available in monitored data SELECTED_GRP.
ASCGAPC allows multiple sources to participate in the voltage and
frequency matching simultaneously, but all the sources nominated for
matching should belong to either participation Group 2 or
participation Group 3.
One of the participating sources (set with Tuning source) is used for the fine tuning of
voltage and frequency. This information is sent to the corresponding source via the
respective output signal ASC_SRC1_DAT...ASC_SRC8_DAT.
Table 1390:
States of MATCH STATUS
Value
1("No request")
2("Request received")
3("No source selection")
4("Correct Src selection")
5("Wrong source selection")
6("Wrong tuning Src Sel")
Table continues on next page
Control functions
Description
The sources which are part of Group 2 or Group 3,
but the network is internally connected and setting
Synchrocheck mode in ASNSCSYN is
"Synchronous"
The sources which are part of Group 2 or Group 3,
but the network is internally connected and the
setting
Synchrocheck mode in ASNSCSYN is
"Asynchronous"
The sources which are part of Group 2 or Group 3,
but the network is internally asynchronous and
Synchrocheck mode in ASNSCSYN is
setting
"Synchronous"
The sources which are part of Group 2 or Group 3,
but setting
Synchrocheck mode in ASNSCSYN is
"Off"
Description
No NSCB is selected for synchronization.
Synchronization request is received.
The request is received and the command
Confirm source Sel is "FALSE".
parameter
The synchronization request is received, the
Confirm source Sel is
command parameter
"TRUE", and the nominated sources belong to
either Group 2 or Group 3.
The synchronization request is received, the
Confirm source Sel is
command parameter
"FALSE", and the nominated sources do not
belong to Group 2 or all belong to Group 3.
The source selected for fine tuning is not among
the nominated sources.
Section 9