Section 9
Control functions
1416
GUID-5A74B1BB-B568-486B-94F8-FE192C0E38ED V1 EN
Figure 761:
Voltage matching pulse generation with variable command pulse
length
Voltage matching with variable command pulse off intervals
When the setting Voltage match mode is set to "Variable Interval", the voltage
matching is done with variable command pulse off intervals.
The voltage match command pulses are now the same length, but the intervals are
inversely proportional to the voltage difference.
Pulse length (tpU): adjustable with the setting Volt pulse Min Dur (tpUmin)
Pulse off interval (tsU): adjustable with the setting Volt pulse off Intv, and also
dependent on settings Voltage Diff Ov Ex and Voltage Diff Un Ex as per
326.
tsU
Volt pulse off Intv
=
GUID-CADE8CDC-64B4-4AC4-876D-ECF3B09FB0F2 V1 EN
ΔU
Measured voltage difference across the CB to be synchronized
Voltage Diff Ov Ex
+ΔUmax Setting
-ΔUmax
Setting
Voltage Diff Un Ex
Reset of voltage raise and lower command pulses
The generated voltage raise and lower command pulses RAISE_U and LOWER_U are
immediately reset if any of the following conditions is met.
During matching of its own CB synchronization
U
(
+
1 0 325
.
U
1MRS759142 C
max
U
max
)
+ −
≥ 0
2
 
Technical Manual
Equation
(Equation 326)
REX640