ABB RELION REX640 Technical Manual page 1301

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
REX640
Technical Manual
2
2
S
S
P
Q
=
=
+
GUID-B3999831-E376-4DAF-BF36-BA6F761230A9 V2 EN
P
Cos
ϕ =
S
GUID-D729F661-94F9-48B1-8FA0-06E84A6F014C V2 EN
The calculated powers are available as function outputs S_INST, P_INST, Q_INST
and the power factor angle as PF_INST.
Depending on the unit multiplier selected with Power unit Mult, the calculated power
values in the monitored data and measurement view are presented in units of
kVA/kW/kVAr or in units of MVA/MW/MVAr.
GUID-171085AB-AD2C-4F8B-919A-200A66BE923F V1 EN
Figure 702:
Complex power and power quadrants
Table 1213:
Power quadrants
Quadrant
Current
Q1
Lagging
Q2
Lagging
Q3
Leading
Q4
Leading
The active power P direction can be selected between forward and reverse with Active
power Dir and correspondingly the reactive power Q direction can be selected with
Reactive power Dir. This affects also the accumulated energy directions.
Measurement functions
P
Q
+
+
-
+
-
-
+
-
Section 8
(Equation 315)
(Equation 316)
PF
Power
0...+1.00
+ind
0...-1.00
-cap
0...-1.00
-ind
0...+1.00
+cap
1295