Section 7
Condition monitoring functions
1268
Name
Type
POSCLOSE
BOOLEAN
OPEN_CB_EXE
BOOLEAN
CLOSE_CB_EXE
BOOLEAN
PRES_ALM_IN
BOOLEAN
PRES_LO_IN
BOOLEAN
SPR_CHR_ST
BOOLEAN
SPR_CHR
BOOLEAN
RST_IPOW
BOOLEAN
RST_CB_WEAR
BOOLEAN
RST_TRV_T
BOOLEAN
RST_SPR_T
BOOLEAN
Table 1194:
SSCBR Output signals
Name
Type
TRV_T_OP_ALM
BOOLEAN
TRV_T_CL_ALM
BOOLEAN
SPR_CHR_ALM
BOOLEAN
OPR_ALM
BOOLEAN
OPR_LO
BOOLEAN
IPOW_ALM
BOOLEAN
IPOW_LO
BOOLEAN
CB_LIFE_ALM
BOOLEAN
MON_ALM
BOOLEAN
PRES_ALM
BOOLEAN
PRES_LO
BOOLEAN
OPENPOS
BOOLEAN
INVALIDPOS
BOOLEAN
CLOSEPOS
BOOLEAN
Default
Description
0=False
Signal for closeposition of apparatus from I/O
0=False
Signal for open command to coil
0=False
Signal for close command to coil
0=False
Binary pressure alarm input
0=False
Binary pressure input for lockout indication
0=False
CB spring charging started input
0=False
CB spring charged input
0=False
Reset accumulation energy
0=False
Reset input for CB remaining life and operation
counter
0=False
Reset input for CB closing and opening travel times
0=False
Reset input for the charging time of the CB spring
Description
CB open travel time exceeded set value
CB close travel time exceeded set value
Spring charging time has crossed the set value
Number of CB operations exceeds alarm limit
Number of CB operations exceeds lockout limit
Accumulated currents power (Iyt),exceeded alarm
limit
Accumulated currents power (Iyt),exceeded
lockout limit
Remaining life of CB exceeded alarm limit
CB 'not operated for long time' alarm
Pressure below alarm level
Pressure below lockout level
CB is in open position
CB is in invalid position (not positively open or
closed)
CB is in closed position
1MRS759142 C
REX640
Technical Manual