Table 1384:
Settings of ASCGAPC of NSCB4 for given example
Settings
ASC CB Num1
Number of sources
Number of NonSrc CB
Src1 bus A Num
Src2 bus A Num
Src3 bus A Num
NonSrc1 bus A1 Num
NonSrc1 bus A2 Num
NonSrc2 bus A1 Num
NonSrc2 bus A2 Num
NonSrc3 bus A1 Num
NonSrc3 bus A2 Num
NonSrc4 bus A1 Num
NonSrc4 bus A2 Num
Table 1385:
Settings of ASCGAPC of SCB1 for given example
Settings
ASC CB Num1
Number of sources
Number of NonSrc CB
Table 1386:
Settings of ASCGAPC of SCB2 for given example
Settings
ASC CB Num1
Number of sources
Number of NonSrc CB
Suggested values
Non source CB 4
3
4
Bus 3
Bus 2
Bus 4
Bus 1
Grid
Bus 1
Bus 2
Bus 2
Bus 3
Bus 3
Bus 4
Suggested values
Source CB 1
3
4
Suggested values
Source CB 2
3
4
Section 9
Control functions
Description
ASC1 host circuit breaker
number 4
Total number of sources present
in system
Number of bus coupler or grid
transformer CB in the system
Source1 CB connected bus A
number
Source1 CB connected bus A
number
Source1 CB connected bus A
number
Non-source CB1 connected bus
A1 number
Non-source CB1 connected bus
A2 number
Non-source CB2 connected bus
A1 number
Non-source CB2 connected bus
A2 number
Non-source CB3 connected bus
A1 number
Non-source CB3 connected bus
A2 number
Non-source CB4 connected bus
A1 number
Non-source CB4 connected bus
A2 number
Description
ASC1 host circuit breaker
number 1
Total number of sources present
in system
Number of bus coupler or grid
transformer CB in the system
Description
ASC1 host circuit breaker
number 2
Total number of sources present
in system
Number of bus coupler or grid
transformer CB in the system