Operation Principle - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
5.6.5
REX640
Technical Manual
Table 1033:
Analog inputs
Input
I3P
See the preprocessing function blocks in this document for the
possible signal sources.
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings. For
troubleshooting, check the contents of this chapter and also the preprocessing blocks
in this document. The configuration can be written to the protection relay once the
mismatch is corrected.

Operation principle

The function can be enabled and disabled with the Operation setting. The
corresponding parameter values are "On" and "Off".
The operation of ESMGAPC can be described using a module diagram. All the
modules in the diagram are explained in the next sections.
I3P
ST_EMERG_RQ
BLOCK
GUID-D0447355-E16A-4A78-A756-E11503853C58 V1 EN
Figure 593:
Functional module diagram
Standstill detector
The module detects if the motor is in a standstill condition. The standstill condition
can be detected based on the phase current values. If all three phase currents are below
the set value of Motor standstill A, the motor is considered to be in a standstill
condition.
Timer
The timer is a fixed 10-minute timer that is activated when the ST_EMERG_RQ input
is activated and motor standstill condition is fulfilled. Thus, the activation of the
ST_EMERG_RQ input activates the ST_EMERG_ENA output, provided that the motor
is in a standstill condition. The ST_EMERG_ENA output remains active for 10
minutes or as long as the ST_EMERG_RQ input is high, whichever takes longer.
The activation of the BLOCK input blocks and also resets the timer.
Protection related functions
Description
Three-phase currents
I_A
Timer
I_B
Standstill
t
detector
I_C
Section 5
ST_EMERG_ENA
1093