Bus A
~
3
CB_A
Z2_START
GUID-7689FC42-E6D9-4B59-8B22-0DF82FCCCB29 V1 EN
Figure 618:
Simplified functional diagram of the permissive underreach scheme
Permissive overrreaching transfer trip scheme POTT
The permissive overreach scheme is enabled with Scheme type = "Permissive
Overreach".
In this scheme, the start signal from the overreaching zone Z2 is connected to the
CSOR input to create a CS_PRM signal. The CS_PRM signal can also be issued
simultaneously from the underreaching zone Z1. In this case, the start signal from the
underreaching zone Z1 is connected to the CSUR input. The duration of the CSUR
input signal is prolonged by the Carrier Min Dur setting to ensure a sufficient duration
of the CS_PRM signal.
In case of parallel feeders, and when the external current reversal logic
(CRWPSCH) is enabled, the CS_PRM signal is not prolonged and the
value of Carrier Min Dur is set to zero to secure correct operation.
In the permissive overreach scheme, the received signal CR_PRM, or CRL if the
unblocking function is enabled, is used to allow the overreaching zone Z2 to trip
(activation of the OPERATE output) after the settable pick-up delay Coordination
Time. The start signal from the overreaching zone is connected to the CACC input.
Activating the BLOCK input totally blocks the permissive overreach scheme. The
CS_PRM and OPERATE outputs can be blocked by the BLK_CS_OPR input.
Protection related functions
Z2
Z1
Z1
Z2
TRIP_CB_A
Z2_START
Z1_START
Section 5
Bus B
~
3
CB_B
TRIP_CB_B
1143