Configurable directional setting when "Neg. seq. volt." selection is
made using the Pol quantity setting
When Zero seq. volt. voltage selection is made using Pol quantity setting, the
directional detector module compares the angle of the residual current to the residual
voltage. Using the residual voltage as reference, the residual current angle is
compared to the Characteristic angle setting. If the angle difference is within the
operating sector selected by the Directional mode setting, the Enable signal is sent to
Timer.
The polarizing quantity (residual voltage) is inverted because of
switched voltage measurement cables, the correction can be done by
setting the Pol reversal setting to "True", which rotates the polarizing
quantity by 180 degrees.
The directional characteristic for the measured or calculated residual
power is same.
Protection related functions