Section 10
Power quality measurement functions
1626
If Phase mode is "Three Phase", the DIPST and INTST outputs are
activated when the voltage levels of all monitored phases, defined
with the parameter Phase supervision, drop below the Voltage Int set
setting value. An example for the detection principle of voltage
interruption for "Three Phase" when Phase supervision is "Ph A + B
+ C", and also the corresponding start signals when Phase mode is
"Single Phase", are as shown in the example for the detection of a
three-phase interruption.
Voltage swell set
U_A
U_C
Voltage dip set
Voltage Int set
SWELLST
DIPST
INTST
SWELLST
DIPST
INTST
GUID-D4FBD014-6CF0-4498-97E8-487EB744D237 V1 EN
Figure 837:
Detection of three-phase voltage interruption
The module measures voltage variation magnitude on each phase separately, that is,
there are phase-segregated outputs ST_A, ST_B and ST_C for voltage variation
indication. The configuration parameter Phase supervision defines which voltage
phase or phases are monitored. If a voltage phase is selected to be monitored, the
function assumes it to be connected to a voltage measurement channel. In other words,
if an unconnected phase is monitored, the function falsely detects a voltage
interruption in that phase.
The maximum magnitude and depth are defined as percentage values calculated from
the difference between the reference and the measured voltage. For example, a dip to
70 percent means that the minimum voltage dip magnitude variation is 70 percent of
the reference voltage amplitude.
A) Three phase mode
B) Single phase mode