• Supply circuit, line fusing, and wire size adequate to the
electrical rating on the chassis nameplate
• Location close to the ED-48000B chassis and easily accessible
• Grounded outlets installed by a licensed electrician,
compatible with the power cords
Note: To maximize fault tolerance, connect each power cord to a separate
power source.
5. Ensure that the blowers in the ED-48000B have access to a total
minimum air flow of 350 cubic feet per minute (595 cubic meters
per hour).
6. Ensure that the air-intake and exhaust vents have a minimum of 2
inches of airspace.
7. Ensure that the air temperature on the air intake side is less than
40 degrees Celsius (104 degrees Farenheit) during operation.
Installation, Setup, and Login
Site planning and safety guidelines
33