Contact the local inspector or City Hall to make sure you are aware of all
federal, state and local codes that could impact the installation. Secure
all required permits before starting the job.
Place the pad high enough to keep rising water from reaching the generator.
Make sure the generator will have adequate and unobstructed airflow by
choosing an open space free of trees, shrubs, buildings or other obstructions.
The unit must be positioned so air vents won't become clogged with leaves,
grass, snow or debris. Make sure that exhaust fumes will not enter the building
through eaves, windows, ventilation fans or other air intakes.

BEFORE YOU BEGIN

MOUNTING PAD

The mounting pad should be located as
close as possible to the transfer switch
and fuel supply. Make sure you leave
adequate room around the generator for
service access. Five feet is a good rule of
thumb, but local codes vary.
Position the electrical conduit for power
wiring, control wiring and the battery
charger circuit so the generator can be
placed correctly on the pad.
The concrete pad should be reinforced
and deep enough so that the weight
of the pad is equal to the weight of the
generator (see Installation Manual).
The length and width of the pad should
exceed the length and width of the
generator by at least 12 inches on all
sides and the pad must be level within ½
inch all around.