Pulse Output Loop Test (Fix Pulse) - Oval EL 2310-0BE Series Instructions Manual

Smart communication unit
Table of Contents

Advertisement

④ Click "Stop" to stop the simulated output. Then a message box (Fig. 89) is displayed. Click "OK" .
⑤ The window for setting the simulated output value is displayed. To exit, click "Cancel".

3.7.2.2 Pulse Output Loop Test (Fix Pulse)

This test can be used to put pulse output into a simulated output state, and to verify the output line
with a loop test.
The test creates simulated output regardless of the process state. If the flowmeter's output is used to
control valves or other such parts, change the control loop to manual control for the sake of safety,
and so that the control loop cannot be influenced by the flowmeter's output.
① Click "Diag/Service (T)" from the menu, and select "Fix Pulse" from the list of "Loop test", then the
following window (Fig. 90) will be displayed.
Setting item
10kHz
Other
② Select the simulated output value. To set a desired output value, click "Other" and enter the value.
By clicking "Start", a message box (Fig. 91) will be displayed. When you click "OK" , the analog
output is generated.
③ During simulated output, a message, "Simulated output is provided now ..." is displayed at the
bottom of the window as shown in Fig. 92.
Detail
10kHz fixed output
Sets a desired output value.
Fig.89
Fig. 90
0.01 to 11000Hz
Fig.91
Fig.92
E-025-2-E
Setting range