3.6.3.5 Output at Error/Alarm (Error output)

① Click "Setup (S)" from the menu, and select "Error output" from the drop-down list of "Outputs",
then the following window (Fig. 48) will be displayed.
② Select for respective items.
Setting item
Analog output at error (Select from the right column.)
No Function: Normal output
Analog error
Downscale: Hold by outputting 2.4mA
output
Zero: Hold by outputting 4.0mA
Hold: Hold current value just before occurrence of error
Upscale: Hold by outputting 21.6mA
Pulse output at error (Select from the right column.)
No Function: Normal output
Pulse error
Zero: 0Hz (Stops pulse output)
output
Hold: Hold the frequency just before occurrence of error
Upscale: Outputs the frequency equivalent to 110% of
NOTE: "Error output" functions when any one of "Overflow Error", "Hardware Failure",
"Parameter Alarm", "Self Diag Alarm", and "Empty Pipe Alarm" occurs. For errors,
refer to "3.11.4 Error/Alarm, Status List".
Fig.47
Fig.48
Detail
metering range.
E-025-2-E
Setting range
No Function, Downscale,
Zero, Hold, Upscale
No Function, Zero, Hold,
Upscale