4 How the SW200i works
During KILL, the control will ignore all signals and close door(s) at normal speed.
If impulse controlled KILL: The operator will resume normal operation after a KILL RESET.
When manual RESET, jumper must be removed and reset button connected to terminal No.
8 and Ground.
Or if state controlled KILL: When KILL signal is no longer active, operator will resume
normal operation.
The behavior of the lock during KILL depends on the group of parameters. See page 65.
The KILL input may be connected to either a normally open contact with GND as reference
or a normally closed contact with QTST as reference, depending of group of parameters,
see page 65.
4.5.2

Function of locks

The lock output only works when the function switch is in OFF or EXIT. If no function
switch is used, OFF or EXIT must be connected to GND (0 VDC).
The control has an available output of DC for external locks
DIP-switches to select 12 or 24 V DC, locked with or without power
DIP-switch for lock release and potentiometer for opening delay
DIP-switch for lock kick to overcome binding in the locking device during closing
Input to unlock signal from lock. Potentiometer for opening delay is to be set to max. As
soon as unlock signal is received the door will start to open. The lock output signal shall be
active low.
If the door cannot fully close, the operator will perform a lock retry (once if manually open,
twice if automatically open).
4.5.3

Panic bar

Panic bar can be disabled by the relay function on the extension board EXU-SA and an external
power supply. Panic bar will then only be active during KILL. See Changing group of parameters
on page 65.
4.5.4

Program selector (wall mounted)

Input for OPEN, EXIT and OFF (if no program selector, AUTO is default).
Note: In OFF-position the operator will comply with the Low Energy Regulation.
4.5.5
Impulses
Input for OUTER impulse, KEY impulse and OPEN/CLOSE impulse.
4.5.6

OPEN/CLOSE impulse

The impulse will open the door and the door will stay open until a new impulse is given. If no
impulse is given the door will close after 15 minutes. This can be made infinite by changing
group of parameters, see page 65.
OPEN/CLOSE impulse works only in program selection AUTO. Can be programmed for OFF
and EXIT as well. See page 65.
12
injury. This mode of operation is most generally used to isolate an area in
the event of a fire.